OM 602RS
6 digit DATA DISPLAY
Type OM 602RS is a 6-digit data display from serial lines RS 232/485 with protocole ASCII, MESSBUS, MODBUS - RTU, PROFIBUS DP, and PROFINET. The instrument is based on a single-chip microcontroller, which ensures good accuracy, stability and easy operation of the instrument.
-
6 digit programmable projection
-
input: RS 232/485
-
ASCII, MESSBUS, MODBUS RTU, PROFIBUS DP, PROFINET
-
digital filter
-
size of DIN 96 x 48 mm
-
power supply 10…30 V AC/DC or 80…250 V AC/DC
Options
-
excitation
-
comparators
-
analog output
-
three-color display - 20 mm
Input
RS
Input
fixed, according to order
RS 232/485
PROFIBUS DP
RS 232/485
PROFIBUS DP
Protocol
ASCII
ASCII - Master
ASCII - Slave
ASCII - Universal
MESSBUS
MODBUS RTU
PROFIBUS DP
ASCII - Master
ASCII - Slave
ASCII - Universal
MESSBUS
MODBUS RTU
PROFIBUS DP
Format
8 bits + no parity + 1 stop bit
7 bits + even parity + 1 stop bit
7 bits + even parity + 1 stop bit
Rate
300…230 400 Baud
9 600…12 MBaud (PROFIBUS)
9 600…12 MBaud (PROFIBUS)
Line termination
short circuit module socket inside the instrument
External inputs
Number
3 inputs, on contact
Functions
| OFF | No function |
| HOLD | Stopping measurement (option: Display - Analog output - Limits) |
| BLOK.K. | Blocking front panel keys |
| B.HESL. | Blocking access to the LIGHT/PROFI menu |
| TARA | Tare activation |
| NUL. TA. | Resetting tare |
| NUL. M.M. | Resetting Min/Max. value |
Projection
Display range
-999…9999, single-coloured 14-segment LED
-99999…999999, single-coloured 14-segment LED
-99999…999999, single-coloured 14-segment LED
Display height
14 mm, 20 mm
Display colour
red, green, red/green/orange
Signalizing LED
| 1, 2, 3, 4 | Limits L1, L2, L3, L4 (red) |
| T | Tare (green) |
| M | Min./Max. value (green) |
Decimal point
menu adjustable - fixed or floating
Display brightness
menu adjustable
Displayed values
| Kan A | Value from channel A |
| Fil. A | Value from channel A after digital filter adjustment |
| Mat. Fn. | Value of mathematical function |
| Max. | Maximum value |
| Min. | Minimum value |
Settings
Control
The device is controlled and set by five buttons on the front panel
Selected functions can also be controlled via external inputs
Selected functions can also be controlled via external inputs
Menu
| LIGHT | contains only items necessary for basic device settings with password access |
| PROFI | Full device settings with password access |
| USER | User menu of any item, selected from LIGHT/PROFI. Access without password. |
Optional functions
Buttons "Left", "Up", "Down", "Enter" can be assigned additional optional features
| ZAKAZ | button has no function |
| NUL. M.M. | Resetting Min/Max vaslues |
| NUL. TA. | Tare reset |
| MENU | Direct access to the selected menu item |
| DOC. H. | Temporary projection of selected values |
| TARA | Activating function Tare |
OM Link
Company communication interface for operation, setting and update of device firmware
OM Link program is also designed for visualization and filing of meas. values from more instruments
OM Link program is also designed for visualization and filing of meas. values from more instruments
Instrument accuracy and functionality
Temperature coefficient
50 ppm/°C
Digital filters
| arithmetic mean | from 2…100 measurements |
| floating mean | from 2…30 measurements |
| exponential mean | from 2…100 measurements |
| rounding | setting projection step for display |
Functions
| Tare | designed to reset display on non-zero input signal |
| Min/max value | registration of min./max. value achieved during measurement |
Math. functions
polynom, 1/x, logarithm, exponential, power, root, sin x
Watch-dog
reset after 400 ms
Calibration
at 25°C and 40 % r.h.
Comparators
Type
Digital, menu adjustable, contact connect. < 30 ms
Mode
| Hysteresis | switch. point, hysteresis band "Mez ± 1/2 Hys." and time (0 ... 99.9 s) determ. switching delay |
| From-To | output interval ON and OFF |
| Dose | period, its multiples and time (0 ... 99.9 s), during which the output is active |
Output
1x relay, switch-over contact (250 VAC/30 VDC, 3 A)
2x relay, switch-over contact (250 VAC/30 VDC, 3 A)
1x relay, switch on contact (250 VAC/30 VDC, 3A)
2x relay, switch on contact (250 VAC/30 VDC, 3 A)
2x bistable relay (250 VAC/30 VDC, 3A)
3x relay, 2x switch on + 1x switch-over contact (250 VAC/30 VDC, 3A)
4x relay, 2x switch on + 2x switch-over contact (250 VAC/30 VDC, 3A)
2x open collector (30 VDC/100 mA)
4x open collector (30 VDC/100 mA)
2x open collector (30 VDC/100 mA) + 2x relay, CO contact (250 VAC/30 VDC, 3 A)
2x SSR (250 VAC/1 A)
2x relay, switch-over contact (250 VAC/30 VDC, 3 A)
1x relay, switch on contact (250 VAC/30 VDC, 3A)
2x relay, switch on contact (250 VAC/30 VDC, 3 A)
2x bistable relay (250 VAC/30 VDC, 3A)
3x relay, 2x switch on + 1x switch-over contact (250 VAC/30 VDC, 3A)
4x relay, 2x switch on + 2x switch-over contact (250 VAC/30 VDC, 3A)
2x open collector (30 VDC/100 mA)
4x open collector (30 VDC/100 mA)
2x open collector (30 VDC/100 mA) + 2x relay, CO contact (250 VAC/30 VDC, 3 A)
2x SSR (250 VAC/1 A)
Analogue outputs
Type
Isolated, programmable with a 16-bit D / A converter, type and range are menu selectable
Temperature coefficient
15 ppm/°C
Nonlinearity
±0,1 % of range
Rate
response to value change < 1 ms
Ranges
0...2 V, 0...5 V, 0...10 V, ±10 V, 0...5 mA, 0...20 mA, 4...20 mA
Compensation
600 Ohm/12 V, 1 000 Ohm/24 V
Error state
at range of 4...20mA
error message indication (<3.0 mA)
Detection of current loop interruption
error message indication (<3.0 mA)
Detection of current loop interruption
Sensor excitation
Adjustable
5…24 VDC/max. 1,2 W
Power supply
Power supply
10…30 V AC/DC, ±10 %, PF > 0,4, I < 40 A/1 ms, isolated
80…250 V AC/DC, ±10 %, PF > 0,4, I < 40 A/1 ms, isolated
80…250 V AC/DC, ±10 %, PF > 0,4, I < 40 A/1 ms, isolated
Current draw
< 9,4 W/9,2 VA
Power supply protection
Power supply is protected by a fuse inside the instrument
Mechanical properties
Dimensions
96 x 48 x 120 mm (w x h x d)
Panel cutout
90,5 x 45 mm (w x h)
Material
Noryl GFN2 SE1, non-inflammable UL 94 V-I
Operating conditions
Connection
connector terminal board, cable section < 1,5/2,5 mm2
Stabilization period
within 15 minutes after switch on
Operating temperature
-20°…60°C
Storage temperature
-20°…80°C
Protection class
IP64 (front panel only)
El. safety
EN 61010-1, A2
Dielectric strength
4 kVAC within 1 min. between pow. supply and input
4 kVAC within 1 min. between pow. supply and data/anal. output
4 kVAC within 1 min. between input and relay output
2,5 kVAC within 1 min.between input and data/anal. output
4 kVAC within 1 min. between pow. supply and data/anal. output
4 kVAC within 1 min. between input and relay output
2,5 kVAC within 1 min.between input and data/anal. output
Insulation resistance
for polution degree II, measuring cat. III.
| power supply | 670 V (ZI), 300 V (Di)* |
| input, output, PN | 300 V (ZI), 150 V (Di)* |
EMC
EN 61326-1
Seismic capacity
IEC 980: 1993, par.6
Datasheets
| File name | File type | Version | Language | Download |
|---|---|---|---|---|
|
ds01_OM602RS_2023.1_en.pdf
ds01_OM602RS_2023.1_cs.pdf
|
PDF
|
2023.1 |
|
Download |
|
ds01_OM602RS_a2020.1_en.pdf
ds01_OM602RS_a2020.1_fr.pdf
ds01_OM602RS_a2020.1_ru.pdf
ds01_OM602RS_a2020.1_cs.pdf
|
PDF
|
2020.1 |
|
Download |
User manuals
| File name | File type | Version | Language | Download |
|---|---|---|---|---|
|
man0100_OMProfi_2020.3_en.pdf
man0100_OMProfi_2020.3_cs.pdf
|
PDF
|
2020.3 |
|
Download |
|
man0101_OMProfibus_a2014.2.1_en.pdf
man0101_OMProfibus_a2014.2.1_cs.pdf
|
PDF
|
2014.2.1 |
|
Download |
| man0101_OMProfibus_a2014.2.0_cs.pdf |
PDF
|
2014.2.0 | cs | Download |
|
man0102_OMProfibus_a2010.1.2_en.pdf
man0102_OMProfibus_a2010.1.2_cs.pdf
|
PDF
|
2010.1.2 |
|
Download |
| man0102_OMProfibus_a2007.1.0_cs.pdf |
PDF
|
2007.1.0 | cs | Download |
| man0102_OMProfibus_a2010.1.1_en.pdf |
PDF
|
2010.1.1 | en | Download |
|
man07_OM602RS_20_2012.3.0_en.pdf
man07_OM602RS_2012.3.0_en.pdf
man07_OM602RS_2012.3.0_cs.pdf
man07_OM602RS_20_2012.3.0_cs.pdf
|
PDF
|
2012.3.0 |
|
Download |
| man08_OM602RS_20_a2010.1.2_cs.pdf |
PDF
|
2010.1.2 | cs | Download |
| man09_OM602RS_a2009.1.3_cs.pdf |
PDF
|
2009.1.3 | cs | Download |
| man010_OM602RS_a2006.1.1_cs.pdf |
PDF
|
2006.1.1 | cs | Download |
|
man010_OM602RS_ModB_2006.1.0_en.pdf
man010_OM602RS_ModB_2006.1.0_cs.pdf
|
PDF
|
2006.1.0 |
|
Download |
Application notes
| File name | File type | Version | Language | Download |
|---|---|---|---|---|
| an01_Informace k OM PROFINET_2020_cs.pdf |
PDF
|
2020 | cs | Download |
|
an01_Handling RealTime memory _2006.01_en.pdf
an01_Obsluha pameti RealTima_2006.01_cs.pdf
|
PDF
|
2006.01 |
|
Download |
|
an02_Firmware upload_2006.02_en.pdf
an02_Upload firmware_2006.02_cs.pdf
|
PDF
|
2006.02 |
|
Download |
| an02_Upload firmware_2014.02_ru.pdf |
PDF
|
2014.02 | ru | Download |
|
an05_MODBUS data protocol_2020.01_en.pdf
an05_MODBUS datový protokol_2020.01_cs.pdf
|
PDF
|
2020.01 |
|
Download |
Certificates
| File name | File type | Version | Language | Download |
|---|---|---|---|---|
|
crt02_EU_Declaration_OM602_2022_en.pdf
crt02_EU_Prohlaseni_OM602_2022_cs.pdf
|
PDF
|
2022 |
|
Download |
|
crt03_Declaration_17050_OM602_2022_en.pdf
crt03_Prohlaseni_17050_OM602_2022_cs.pdf
|
PDF
|
2022 |
|
Download |
Firmware
| File name | File type | Version | Language | Download |
|---|---|---|---|---|
| fw01_OM 602RS 77-602_2020_xx.hex |
HEX
|
2020 | xx | Download |
Software
| File name | File type | Version | Language | Download |
|---|---|---|---|---|
|
sw03_GSD OM-Profibus_2020_xx.zip
sw03_GSD OM-Profibus_2020_xx.zip
|
ZIP
|
2020 |
|
Download |
|
sw04_GSDML OM-Profinet_2020.2.33_xx.zip
sw04_GSDML OM-Profinet_2020.2.33_xx.zip
|
ZIP
|
2020.2.33 |
|
Download |
| sw05_GSDML OM-Profinet_2024.2.33_xx.zip |
ZIP
|
2024.2.33 | xx | Download |
CAD
| File name | File type | Version | Language | Download |
|---|---|---|---|---|
| drw01_OM Krabicka_2014_xx.dwg |
DWG
|
2014 | xx | Download |