OMR card - IN.05
IN.05 - 5x Input for Pt/Ni/Cu sensors
Plug-in card for measuring resistance sensors is fully isolated from the internal bus with a galvanic isolation also between individual outputs.
The design of the cards allows their use at any position in the device. If during the use of the device appear new requirements to increase the number of inputs or outputs, just order another card and insert it into a free slot. In this manner the device can "grow" with your requirements.
-
5x Analogue input
-
Pt 50/100/1000, Ni 1000/10 000, Cu 50/100
Input
*
Number of inputs
5 inputs
OHM
Range
menu selectable
0…100 Ohm
0…300 Ohm
0…1 kOhm
0…3 kOhm
0…10 kOhm
0…30 kOhm
0…100 Ohm
0…300 Ohm
0…1 kOhm
0…3 kOhm
0…10 kOhm
0…30 kOhm
Connection
2, 3 or 4-wire
RTD
Type
menu selectable
EU > 100/500/1 000 Ohm s 3 850 ppm/°C
-50°…450°C
Connection
2, 3 or 4-wire
Ni
Type
menu selectable
Ni 1 000/10 000 s 6 180 ppm/°C
-50°…250°C
Connection
2, 3 or 4-wire
Cu
Type
menu selectable
Cu 50/100 with 4 280 ppm/°C
-200°…200°C
Connection
2-, 3-, or 4-wire
Instrument accuracy and functionality
Temperature coefficient
50 ppm/°C
Accuracy
±0,2 % of range + 1 digit
(for 10 measur./s)
(for 10 measur./s)
Rate
5…320 measur./s
Wire compensation (RTD, OHM)
< 40/100 Ohm
Digital filters
| floating mean | from 2…30 measurements |
| exponential mean | from 2…100 measurements |
Functions
| Tare | designed to reset display on non-zero input signal |
Watch-dog
reset after 500 ms
Calibration
at 25°C and 40 % r.h.
Power supply
Power supply
interní sběrnice 5 VDC,24 VDC/max.150 mA
Current draw
< 0,75 W
Mechanical properties
Dimensions
65 x 98 mm
Installation
plug-in card
Operating conditions
Connection
connector terminal board, cable section < 1,5 mm2
Operating temperature
-20°…60°C
Storage temperature
-20°…85°C
Protection class
IP00
El. safety
EN 61010-1, A2
Dielectric strength
2,5 kVAC within 1 min. between bus and inputs
1 kVAC within 1 min. between inputs
1 kVAC within 1 min. between inputs
Insulation resistance
for polution degree II, measuring cat. III.
| input, bus | 300 V (ZI), 150 V (Di)* |
| input, input | 150 V (ZI), 100 V (Di)* |
EMC
EN 61326-1
Seismic capacity
IEC 980: 1993, par.6
User manuals
| File name | File type | Version | Language | Download |
|---|---|---|---|---|
|
Operating instructions OMR700_IN05
Návod OMR700_IN05
|
PDF
|
2019.2 |
|
Download |
Certificates
| File name | File type | Version | Language | Download |
|---|---|---|---|---|
|
Certificate EU_Declaration_OMR700
Certifikát EU_Prohlášení_OMR700
|
PDF
|
2024 |
|
Download |
|
Certificate Declaration_17050_OMR700
Certifikát Prohlaseni_17050_OMR700
|
PDF
|
2022 |
|
Download |
|
Certificate Seismic_test_OMR700
Certifikát Seizmicka_zkouzka_OMR700
|
PDF
|
2016 |
|
Download |