OMR card - IN.15
IN.15 - 3-phase wattmeter
Plug-in card for measurements of 3-phase power, voltage (VRMS), current (ARMS), frequency (Hz), power P, Q, S, harmonic distortion, angle and cos fi for the OMR 700 is fully isolated from the internal bus with a galvanic isolation also between individual inputs.
The design of the cards allows their use at any position in the device. If during the use of the device appear new requirements to increase the number of inputs or outputs, just order another card and insert it into a free slot. In this manner the device can "grow" with your requirements.
-
1x Analogue 3-F input, isolated
-
input U: 0…250 V
input I: 0…1 / 5 A
Input
*
Number of inputs
1 vstup, izolovaný
AC
No. of phases
3
Range
0…250 V
< 1 MOhm
0…1 A
< 150 mV
0…5 A
< 150 mV
Input frequency
50/60 Hz
pro amplitudu do 50 V
pro amplitudu do 50 V
Measured variables
Voltage (Vrms)
Current (Irms)
Real power (P-W)
Jalový výkon (Q)
Zdánlivý výkon (S)
Frequency (Hz)
Harmonické zkreslení
Úhel
Účiník
Current (Irms)
Real power (P-W)
Jalový výkon (Q)
Zdánlivý výkon (S)
Frequency (Hz)
Harmonické zkreslení
Úhel
Účiník
Instrument accuracy and functionality
Temperature coefficient
50 ppm/°C
Accuracy
0,3 % of range
(for 5 measur./s)
(for 5 measur./s)
Rate
10 periods
Overload capacity
2x; 10x (t < 30 ms) - not for > 250 V and 5 A
Watch-dog
reset after 500 ms
Calibration
at 25°C and 40 % r.h.
Power supply
Power supply
interní sběrnice 5 VDC,24 VDC
Current draw
< 2,5 W
Mechanical properties
Dimensions
65 x 98 mm
2 cards
2 cards
Installation
plug-in card
Operating conditions
Connection
connector terminal board, cable section < 2,5 mm2
Operating temperature
-20°…60°C
Storage temperature
-20°…85°C
Protection class
IP00
El. safety
EN 61010-1, A2
Dielectric strength
2,5 kVAC within 1 min. between bus and inputs
1 kVAC within 1 min. between inputs
1 kVAC within 1 min. between inputs
Insulation resistance
for polution degree II, measuring cat. III.
| input, bus | 300 V (ZI), 150 V (Di)* |
| input, input | 300 V (ZI), 100 V (Di)* |
EMC
EN 61326-1
Seismic capacity
IEC 980: 1993, par.6
User manuals
| File name | File type | Version | Language | Download |
|---|---|---|---|---|
|
Operating instructions OMR700_IN15
Návod OMR700_IN15
|
PDF
|
2019.2 |
|
Download |
Certificates
| File name | File type | Version | Language | Download |
|---|---|---|---|---|
|
Certificate EU_Declaration_OMR700
Certifikát EU_Prohlášení_OMR700
|
PDF
|
2024 |
|
Download |
|
Certificate Declaration_17050_OMR700
Certifikát Prohlaseni_17050_OMR700
|
PDF
|
2022 |
|
Download |
|
Certificate Seismic_test_OMR700
Certifikát Seizmicka_zkouzka_OMR700
|
PDF
|
2016 |
|
Download |