OMX 333iUNI
UNIVERSAL ISOLATED TRANSMITTER • UNI > U/I
The OMX 333i model series are simple DIN rail mountable programmable transmitters.
Type OMX 333iUNI is a multifunctional transmitter with the possibility of 10 input configurations easily adjustable in the instrument´s menu. This device is based on a microprocessor with a 24-bit ∆∑ A/D converter and D/A converter, which ensures good accuracy, stability and easy operation of the instrument.
-
Multifunction input (DC, PM, RTD, T/C, DU)
-
Configurable type and measuring range
-
Analogue output, Relay/Transistor Outputs
-
Excitation 24 V
-
Teach-in, Digital filters, Tare, Linearization, Simulation
-
Quick configuration by DIP switch
-
PC configurable via USB port
-
Galvanic isolation 2.5 kVA
-
Power supply 10…30 VDC / 24 VAC
Input
*
Number of inputs
1 input
DC
Range
menu selectable
±60 mV
> 10 MOhm
Vstup 3
±75 mV
> 10 MOhm
Vstup 3
±100 mV
> 10 MOhm
Vstup 3
±150 mV
> 10 MOhm
Vstup 3
±300 mV
> 10 MOhm
Vstup 3
±1000 mV
> 10 MOhm
Vstup 3
±20 V
> 1 MOhm
Vstup 1
±40 V
> 1 MOhm
Vstup 1
±100 mA
> 200 mV
Vstup 5
PM
Range
menu selectable
±2 V
1 MOhm
Input 1
±5 V
1 MOhm
Input 1
±10 V
1 MOhm
Vstup 1
±5 mA
< 200 mV
Input 5
±20 mA
< 200 mV
Input 5
4…20 mA
< 200 mV
Input 5
OHM
Range
menu selectable
0…100 Ohm
0…300 Ohm
0…1 kOhm
0…3 kOhm
0…10 kOhm
0…30 kOhm
0…100 kOhm
0...300 kOhm (only for 2 or 4-wire connection)
0…100 Ohm
0…300 Ohm
0…1 kOhm
0…3 kOhm
0…10 kOhm
0…30 kOhm
0…100 kOhm
0...300 kOhm (only for 2 or 4-wire connection)
Connection
2, 3 or 4-wire
RTD
Type
menu selectable
Pt 100/500/1000, 3850 ppm/°C
-50°...450°C
Pt 100 3920 ppm/°C
-50°...450°C
Pt 50 3910 ppm/°C
-200°...1100°C
Pt 100 3910 ppm/°C
-200°...450°C
Connection
2, 3 or 4-wire
NTC
Type
selectable in the menu
NTC1 2k2, B2585=3600 (-40°...125°C)
NTC2 2k0, B2585=3528 (-40°...125°C)
NTC3 10k, B2585=3435 (-40°...125°C)
NTC4 10k, B2585=3977 (-40°...125°C)
NTC5 12k, B2585=3740 (-40°...125°C)
NTC6 20k, B2585=4263 (-40°...125°C)
NTC1 2k2, B2585=3600 (-40°...125°C)
NTC2 2k0, B2585=3528 (-40°...125°C)
NTC3 10k, B2585=3435 (-40°...125°C)
NTC4 10k, B2585=3977 (-40°...125°C)
NTC5 12k, B2585=3740 (-40°...125°C)
NTC6 20k, B2585=4263 (-40°...125°C)
Connection
2, 3 or 4-wire
PTC
Type
KTY 81/210
Conection
2,3 or 4-wire
Ni
Type
menu selectable
Ni 1 000/10 000 s 5 000 ppm/°C
-50°…250°C
Ni 1 000/10 000 s 6 180 ppm/°C
-50°…250°C
Connection
2, 3 or 4-wire
Cu
Type
menu selectable
Cu 50/100 with 4 260 ppm/°C
-50°…200°C
Cu 50/100 with 4 280 ppm/°C
-200°…200°C
DU
Potentiometer power supply
1,65 VDC/3 mA, odpor potenciometru > 500 Ohm
External inputs
Number
2 inputs, on contact
Functions
| OFF | No function |
| HOLD | Stopping measurement (option: Display - Analog output - Limits) |
| LOCK | Blocking front panel keys |
| TARA | Tare activation |
| NUL. TA. | Resetting tare |
| NUL. M.M. | Resetting Min/Max. value |
| ROZ.LIM. | Rozepnuti relé/OC (Typ TRVALE) |
| VZOREK | Spuštění jednorázového měření |
| HLD.MIN | HOLD - Hodnota minima* |
| HLD.MAX | HOLD - Hodnota maxima* |
| HLD.M-M | HOLD - Hodnota MAX-MIN* |
| * | Hodnota se počítá z periody od předchozí aktivace externího vstupu |
Settings
Control
The device is controlled and set by two buttons on the front panel
Optional functions
| TARE | Activating function Tare |
| Teach-in | setting the analog input range |
OM Link
Company communication interface for operation, setting and update of device firmware (microUSB)
OM Link program is also designed for visualization and filing of meas. values from more instruments
OM Link program is also designed for visualization and filing of meas. values from more instruments
Instrument accuracy and functionality
Temperature coefficient
50 ppm/°C
Accuracy
0,07 % z rozsahu
0,05 % z rozsahu
DC, PM
0,1 % z rozsahu
OHM - 100/300 k
Accuracy of cold junction measurement
±1,5°C
Rate
1…400 měření/s
rychlost 400 měř/s je se FFT filtrací signálu
rychlost 400 měř/s je se FFT filtrací signálu
Overload capacity
2x; 10x (t < 30 ms)
Wire compensation (RTD, OHM)
< 30 Ohm
Cold junction compensation
adjustable -20°…99°C, automatic
Linearization
lineární interpolací v 100 bodech (pouze přes OM Link)
Digital filters
| arithmetic mean | from 2…100 measurements |
| floating mean | from 2…30 measurements |
| exponential mean | from 2…100 measurements |
| Zaokrouhlení | nastavení pevného kroku pro změnu hodnoty |
Functions
| Tare | designed to reset display on non-zero input signal |
| Fixed tare | preset fixed tare |
| Min/max value | registration of min./max. value achieved during measurement |
| Peak value | display shows only max. or min. values |
| Teach-in | semiautomatic regime of input calibration |
| Simulace | simulace vstupního signálu/funkce přístroje |
| Odložený start | čas kdy se neprovádí měření po připojení přístroje k napájení |
Math. functions
polynom, invertní polynom, 1/x, logarithm, exponential, power, root
Watch-dog
reset after 500 ms
Calibration
at 25°C and 40 % r.h.
Comparators
Number of
2 outputs
Type
Digital, menu adjustable, contact connect. < 30 ms
Mode
| AKT.NAD | Aktivní nad nastavenou hodnotou |
| AKT.POD | Aktivní pod nastavenou hodnotou |
| OKENKO | aktivní v nastaveném okně / pásmu |
| DAVKA | aktivní v nastavených periodách |
Realy functions
| SW.ON | contact closed when active |
| SW.OFF | contact open when active |
| PULSE | closes once for a moment |
| LATCH | contact on untill disarmed |
Output
2x relay, switch-over contact (250 VAC/50 VDC, 3 A)
2x open collector (30 VDC/100 mA)
2x open collector (30 VDC/100 mA)
LED indication
Analogue outputs
Number of outputs
1 output
Type
Isolated, programmable with a 16-bit D / A converter, type and range are menu selectable
Temperature coefficient
15 ppm/°C
Nonlinearity
±0,1 % of range
Accuray
±0,02 % full scale
Rate
response to value change < 1 ms
Ranges
0…2 / 5 / 10 V, ±10 V, resistive load > 1 k?
0…5 / 20 mA / 4…20 mA, comp. < 600 Ohm / V
0…5 / 20 mA / 4…20 mA, comp. < 600 Ohm / V
Error state
error message indication (<3.0 mA)
Detection of current loop interruption
Detection of current loop interruption
Data outputs
Number of outputs
1 outputs
Type
RS 485, isolated
Protocol
MODBUS - RTU
Data format
| Format | 8bit + parity + stop bit |
| Parity | none / even / odd |
| Stop bit | 1 / 1.5 / 2 |
Rate
600…230 400 Baud
Address
| MODBUS | < 246 instruments |
Line termination
by internal resistor 120 Ohm
Sensor excitation
Fixed
24 VDC/60 mA, isolated
Power supply
Power supply
10…30 VDC/24 VAC, ±10 %, PF > 0,4, I < 45 A/1 ms, isolated
Current draw
< 2,4 W/2,6 VA
Power supply protection
Power supply is protected by a fuse inside the instrument
Operating conditions
Connection
connector terminal board, cable section < 1,5/2,5 mm2
Stabilization period
within 5 minutes after switch on
Operating temperature
-20°…60°C
Storage temperature
-20°…80°C
Operating humidity
< 95 % r.v., nekondenzující
Protection class
IP20
El. safety
EN 61010-1, A2
Dielectric strength
2,5 kVAC within 1 min. between pow. supply and input
2,5 kVAC po 1 min. mezi vstupem a výstupem
4 kVAC within 1 min. between input and relay output
2,5 kVAC po 1 min. mezi vstupem a výstupem
4 kVAC within 1 min. between input and relay output
Insulation resistance
for polution degree II, measuring cat. III.
| power supply | 300 V (ZI)* |
EMC
EN 61326-1
RoHS
IEC 63000 : 2018
Seismic capacity
IEC/IEEE 60980-344 ed. 1.0:2020, par 6,9
Mechanical durability
EN 60068-2-6 ed. 2:2008
Datasheets
| File name | File type | Version | Language | Download |
|---|---|---|---|---|
|
Datasheet OMX333iUNI
Katalogový list OMX333iUNI
|
PDF
|
2023.1 |
|
Download |
Certificates
| File name | File type | Version | Language | Download |
|---|---|---|---|---|
|
Certificate EU_Declaration_OMX333
Certifikát EU_Prohlaseni_OMX333
|
PDF
|
2022 |
|
Download |
|
Certificate Declaration_17050_OMX333
Certifikát Prohlaseni_17050_OMX333
|
PDF
|
2022 |
|
Download |
|
Certificate Seismic_test_OMX333
Certifikát Seizmicka_zkouzka_OMX333
|
PDF
|
2015 |
|
Download |
CAD
| File name | File type | Version | Language | Download |
|---|---|---|---|---|
| OMX333iUNI_Out |
STEP
|
2023 | xx | Download |
| OMX333iUNI_Out_Relay |
STEP
|
2023 | xx | Download |
| OMX333iUNI_Relay |
STEP
|
2023 | xx | Download |