Skip to main content

OMX 39DU

OMX 39DU

ISOLATED TRANSMITTER • LIN. POTENTIOMETER > U/I

The OMX 39 model series are inexpensive and simple DIN rail mountable analog transmitters.
Type OMX 39DU is a transmitter for galvanic isolation of linear potentiometers.
The transmitters have galvanic separation with insulation voltage of  600 V. They are therefore suitable as primary insulation for majority of industrial applications.

  • input for linear potentiometer
  • output: 0…5 mA, 0…20 mA, 4…20 mA, ±20 mA
    0…2 V, 0…5 V, 0…10 V, ±10 V
  • galvanic isolationN: 3,75 kVAC
  • width 22 mm
  • DIN rail mounting
  • power supply 10…30 V AC/DC or 80…250 V AC/DC

 

Input
DU
Range
0,1…100 kOhm
Potentiometer power supply
10 VDC/20 mA, potentiometer resistance > 500 Ohm
Settings
Control
The device is designed for simple measurement without further control
By trimmers, accessible from the front of the transducer, you can adjust the output signal within the range of ±10 %
Instrument accuracy and functionality
Temperature coefficient
50 ppm/°C
Accuracy
±0,2 % of range
Rate
Continuous measurement
Overload capacity
2x; 10x (t < 30 ms)
Calibration
at 25°C and 40 % r.h.
Analogue outputs
Type
Isolated, fixed setting
Temperature coefficient
50 ppm/°C
Rate
response to value change < 1 s
Ranges
0...2 V, 0...5 V, 0...10 V, ±10 V (minimum load 1 kOhm), 0...5 mA, 0...20 mA, 4...20 mA, ±20 mA
Compensation
600 Ohm/12 V
Power supply
Power supply
10…30 V AC/DC, ±10 %, PF > 0,4, I < 40 A/1 ms, isolated
80…250 V AC/DC, ±10 %, PF > 0,4, I < 40 A/1 ms, isolated
Current draw
< 2,4 W/2,6 VA
Power supply protection
Power supply is protected by a fuse inside the instrument
Operating conditions
Connection
connector terminal board, cable section < 2,5 mm2
Stabilization period
within 5 minutes after switch on
Operating temperature
-20°…60°C
Storage temperature
-20°…80°C
Protection class
IP20
El. safety
EN 61010-1, A2
Dielectric strength
4 kVAC within 1 min. between pow. supply and input
4 kVAC within 1 min. between pow. supply and analogue output
3,75 kVAC within 1 min. between input and analogue output
Insulation resistance
for polution degree II, measuring cat. III.
power supply 600 V (ZI), 300 V (Di)*
input, output, PN 500 V (ZI), 250 V (Di)*
EMC
EN 61326-1
Mechanical properties
Material
PA 66, non-inflammable UL 94 V-I (blue)
Dimensions
22 x 98 x 113 mm (w x h x d)
Installation
DIN rail, width 35 mm
Images
Connection
Dimensions and installation
To assemble the order, first select the desired instrument configuration.
OMX 39DU-??
Power supply
Any
?
Any
?
10...30 V DC/AC
0
80...250 V DC/AC
1
Analogue output
Any
?
Any
?
0...2 V
1
0...5 V
2
0...10 V
3
0...20 mA
4
4...20 mA
5
±10 V
6
±20 mA
7
0...5 mA
8
Selected combination is invalid
For the selected combination there are no devices in stock

User manuals

File name File type Version Language Download
Operating instructions OMX39
Návod OMX39
PDF
2009.1.0
Download
Návod OMX39
Operating instructions OMX39
PDF
2008.1.0
Download
Show all ↓ Hide ↑